白云Design and calculation of industrial coolers
白云
白云
:本文围绕工业冷却器的设计与计算展开,阐述了工业冷却器在工业生产中的关键作用,其能有效地降低设备或工艺流程的温度,保障系统稳定运行,详细介绍了设计环节,包括依据不同的工业场景和冷却需求确定冷却器的类型,如风冷式、水冷式等,同时考虑冷却介质的特性、流量等参数,在计算方面,着重讲解了热负荷的计算方法,通过分析被冷却对象的热量产生速率、环境温度等因素,精准计算出所需的换热量,还涉及冷却器传热面积、传热系数等关键参数的计算,以确保冷却器能达到预期的冷却效果。
白云1、Design basis
白云
白云Design Standard for Steel Structures GB50017-2017Steel Structure Design Manual, China Construction Industry Press, January 2004
Code for Construction and Acceptance of Steel Structures (GB50205-2020)
白云
British Code for Design of Steel Structures (BS5950)
白云
2、Design load
Load includes structural self weight, wind turbine constant load, live load, snow load, wind load, etc. The structural calculation adopts the ultimate stress method, therefore, the load value is larger than usual. The surface load is calculated based on the distribution coefficient and applied to the platform according to the line load. The wind load is calculated based on the wind vibration coefficient, body shape coefficient, and basic wind pressure to calculate the wind pressure values on four surfaces, which are then converted into line loads and applied to the columns. Auxiliary components such as stair handrails are applied to the stairs according to uniformly distributed loads.
白云
1. Constant load
The self weight of the steel structure is automatically calculated by the program, and the node weight is considered based on the self weight of the structure multiplied by 1.3. The weight and fluid load of the radiator are applied by external forces.
Platform constant load: 0.50kN/m2
白云2. Live load
Live load of the platform for loading: 2.5kN/m2
3. Snow load
白云According to relevant design data, the snow pressure can be basically calculated as 0.4N/m2.
白云
白云4. Wind load
白云
Calculate according to the maximum value.
白云
Basic wind pressure: 0.35kN/m2, height variation coefficient of 1.8, wind vibration coefficient: 1.5, ground roughness category: Class A
白云
白云Class.
白云
白云Is the standard value of wind load, is the wind vibration coefficient at height Z, is the shape coefficient of wind load, and is the coefficient of wind pressure height variation.
白云
白云When the standard value of wind load is less than 0.75kpa, calculate based on 0.75 kPa and multiply by 1.4 times the safety factor. Namely
白云
白云5. Temperature load
白云
白云The temperature difference is relatively small. The structural form is single, and the linear expansion of steel has a relatively small impact on the overall performance of the structure, which can be ignored.
白云6 Earthquake loads
白云
白云According to the seismic analysis design method: small earthquakes do not damage, medium earthquakes are repairable, and large earthquakes do not collapse. Small earthquake analysis can be divided into: bottom shear force method, response spectrum analysis, and elastic time history analysis. Medium earthquake analysis is calculated by multiplying small earthquake analysis by amplification factor.
白云
白云Seismic fortification intensity: 8 degrees
白云
Design basic seismic acceleration peak value: 0.3g
白云
Construction site category: II site
Design grouping: Second group
白云Damping ratio: 0.05
白云
This structure adopts MIADS software for overall modeling and analysis. During modeling, beam elements are mainly used for each structure. In order to facilitate loading, plate elements are established at the structural platform. Consolidation is used as the boundary condition at the bottom of each column, and constraints are applied at the connection between the column and the original structure according to the actual situation. The structure includes upright column, cross brace, slant support and upper and lower platform steel structure.
Load sub factors and load combinations:
白云
白云Number | load | Partial coefficient remarks 白云 | Partial coefficient remarks 白云 |
白云1 白云 | dead load | 白云1.3 | |
2 | Dead load, when it has a restraining effect on uplift and overturning 白云 | 白云1.0 | |
白云3 | Dead load, when acting together with wind load and live load | 白云1.2 | |
4 | 白云Live load | 1.6 白云 | |
5 白云 | Live load, when combined with wind load 白云 | 白云1.2 白云 | |
6 | Wind load 白云 | 1.4 | |
白云7 白云 | 白云When combined with wind load and live load | 1.2 白云 |
白云3、 Radiator calculation
白云1. Material parameters
白云Aluminum alloy adopts 6005-T1, with tensile strength and yield strength equivalent to 6063-T5, tensile strength ≥ 150Mpa, yield stress ≥ 110 Mpa. According to the performance table of aluminum alloy, it is found that 6063-T5 has a tensile strength of 185Mpa, yield stress of 145 Mpa, and fatigue strength of 90MPa.
白云
2. Working condition analysis
白云
The calculation of radiators can be divided into 1. lifting ondition,
白云
3. operating condition (operating condition is divided into
白云
白云4.support and lifting point participate in force simultaneously.
白云
5.support bears gravity, while lifting point bears horizontal force.
白云6.support does not bear any force, that is, when the overall structure is subjected to uneven settlement, there is a suspension at the bottom)
白云
白云To ensure its stability, it is recommended that the foundation treatment should be pre compressed and settlement assessment should be carried out during the overall installation.
白云2.1 Hoisting conditions
白云
At this point, the radiator is only considered for its own weight due to the lack of fluid injection, and is lifted and installed through a side lifting point. Because no other accessories were installed during modeling, in order to estimate the weight more accurately, its self weight coefficient was defined as 1.3.
白云
白云The radiator structure consists of 1, frame 2, support beam 3, heat exchange tube 4, tube plate, and other ancillary structures. As the heat exchange tube and support beam are fixed together through a corrugated plate, it can be considered that the heat exchange tube participates in the structural stress, which leads to strain and stress generation.
白云
白云The overall structural model is
白云
白云Radiator structural model
白云
白云
The overall deformation of the radiator during the lifting process
白云Stress cloud diagram of radiator during lifting process
白云
From its displacement cloud map, it can be seen that its overall deformation is 1.2mm, and the maximum stress is 15MPa
白云Stress cloud map of heat sink
白云
白云
白云
白云
白云Displacement cloud map of heat sink
From its displacement cloud map, it can be seen that its overall deformation is 1mm and the maximum stress is 2MPa. Through calculation, it can be seen that horizontal lifting has little effect on the heat dissipation fins, and its deformation and stress are far less than the standard requirements.
The vertical lifting situation is as follows:
白云
白云Vertical lifting stress cloud map
白云
白云